LOGO! hardware series
LOGO!Soft Comfort lets you create programs for LOGO! devices of various series. Differences are found in the performance, memory space, number of program blocks (for example, flag blocks) and in the structure of the devices.
| Because there are device-specific differences with regard to the functions, you are forced not only to distinguish between the LOGO! versions, but also to take their version status into account. You can identify the version status by the suffix of the LOGO! order number. The current LOGO! versions belong to the 8th generation. They can be identified by the last digits of their order number: 0BA7. You can identify the first three generations of LOGO! devices by the 0, 1 and 2 suffix. The major difference in the first three generations of LOGO! lies in their modular structure. Long and AS-Interface versions are no longer available as of version 0BA3. The standard devices are now equipped with an expansion interface, to which you can connect expansion modules (digital/analog and bus modules) for adapting the LOGO! to suit your personal requirements. This modular structure, however, has little to no influence on programming. You can still program your LOGO! in the usual way. All you have to take into consideration is that AS-Interfaces and analog I/Os are determined by the position at which the relevant expansion module is installed. |
Current devices
Version | Name | Order no. |
|---|---|---|
Standard | LOGO! 12/24RC | 6ED1 052-1MD00-0BA6 |
Standard | LOGO! 24 | 6ED1 052-1CC00-0BA6 |
Standard | LOGO! 24C | 6ED1 052-1CC01-0BA6 |
Standard | LOGO! 24RC | 6ED1 052-1HB00-0BA6 |
Standard | LOGO! 230RC | 6ED1 052-1FB00-0BA6 |
Standard | LOGO! 12/24RCo | 6ED1 052-2MD00-0BA6 |
Standard | LOGO! 24RCo | 6ED1 052-2HB00-0BA6 |
Standard | LOGO! 230RCo | 6ED1 052-2FB00-0BA6 |
Standard | LOGO! 24o | 6ED1 052-2CC00-0BA6 |
Standard | LOGO! 24Co | 6ED1 052-2CC01-0BA6 |
Standard | LOGO! 12/24 RCE * | 6ED1052-1MD00-0BA7 |
Standard | LOGO! 230RCE (AC/DC) | 6ED1052-1FB00-0BA7 |
Memory space is identical for all these devices.
The following expansion modules are available for the standard devices
Version | Name | Order no. |
|---|---|---|
Digital | LOGO! DM8 230R | 6ED1 055-1FB00-0BA1 |
Digital | LOGO! DM16 230R | 6ED1 055-1FB10-0BA0 |
Digital | LOGO! DM8 24 | 6ED1 055-1CB00-0BA0 |
Digital | LOGO! DM16 24 | 6ED1 055-1CB10-0BA0 |
Digital | LOGO! DM8 12/24R | 6ED1 055-1MB00-0BA1 |
Digital | LOGO! DM8 24R | 6ED1 055-1HB00-0BA0 |
Digital | LOGO! DM16 24R | 6ED1 055-1NB10-0BA0 |
Digital | LOGO! AM2 | 6ED1 055-1MA00-0BA0 |
Analog | LOGO! AM2 PT100 | 6ED1 055-1MD00-0BA0 |
Analog | LOGO! AM2 AQ | 6ED1 055-1MM00-0BA1 |
Analog | LOGO! AM2 RTD | 6ED1 055-1MD00-0BA1 |
Text display | LOGO! TD | 6ED1 055-4MH00-0BA0 |
You can use the description to read off the different properties of LOGO!:
12 means 12 V Version
24 means 24 V Version
230 means 115/230 V Version
R means relay outputs (without R transistor outputs)
C means integrated time/timer switch
o means without display
E means the LOGO! … E version
Current devices
The following memory cards and battery cards are available for LOGO! 0BA6 devices:
Description | Order number |
|---|---|
Memory card | 6ED1 056-1DA00-0BA0 |
Battery card | 6ED1 056-6XA00-0BA0 |
Combined memory and battery card | 6ED1 056-7DA00-0BA0 |
LOGO! 0BA7 supports standard SD (Secure Digital) cards that support FAT12, FAT16, or FAT32 file system format. You can store and copy-protect a circuit program, with or without the data log of process data, from a LOGO! 0BA7 to an SD card, or copy a circuit program from the card to a LOGO! 0BA7. You can buy standard SD cards from the market if necessary.
| Note LOGO! 0BA7 only supports SD cards with a maximum memory capacity of 8 GB and a maximum data transfer speed of 48 Mbits/s or 6 MB/s (Class 6). |
You can also use the following available SIMATIC Memory cards for data storage:
Desciption | Order number |
|---|---|
SIMATIC Memory Card 2 MB | 6ES7 954-8LB00-0AA0 |
SIMATIC Memory Card 24 MB | 6ES7 954-8LF00-0AA0 |
Special functions, depending on LOGO! versions
Special function | 0BA0 Standard | 0BA0 ...L | 0BA0 ...LB11 | 0BA1 all | 0BA2 all | 0BA3 all | 0BA4 all | 0BA5 all | 0BA6 all | 0BA7 all |
|---|---|---|---|---|---|---|---|---|---|---|
On delay | X | X | X | X | X | X | Xr | Xr | Xr | Xr |
Off delay | X | X | X | X | X | X | Xr | Xr | Xr | Xr |
Retentive on delay | X | X | X | X | X | X | Xr | Xr | Xr | Xr |
On/off delay | - | - | - | - | X | X | Xr | Xr | Xr | Xr |
Latching relay | X | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr |
Pulse relay | X | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr |
Wiping relay | - | X | X | X | X | X | Xr | Xr | Xr | Xr |
Edge-triggered wiping relay | - | - | - | - | X | X | Xr | Xr | Xr | Xr |
Weekly timer)* | X | X | X | X | X | X | X | X | X | X |
Yearly timer)* | - | - | - | X | X | X | X | X | X | X |
Up/Down counter | X | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr |
Hours counter | - | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr | Xr |
Symmetrical pulse generator | X | X | X | X | X | X | X | X | X | X |
Asynchronous pulse generator | - | - | - | X | X | X | Xr | Xr | Xr | Xr |
Random generator | - | - | - | - | X | X | X | X | X | X |
Threshold trigger | - | X | X | X | X | X | X | X | X | X |
Analog threshold trigger | - | - | - | - | X | X | X | X | X | X |
Analog comparator | - | - | - | - | X | X | X | X | X | X |
Stairway lighting switch | - | - | - | - | X | X | Xr | Xr | Xr | Xr |
Multiple function switch | - | - | - | - | X | X | Xr | Xr | Xr | Xr |
Message text | - | - | - | - | X | X | X | X | X | X |
Softkey | - | - | - | - | - | Xr | Xr | Xr | Xr | Xr |
Shift register | - | - | - | - | - | - | Xr | Xr | Xr | Xr |
Analog watchdog | - | - | - | - | - | - | Xr | Xr | Xr | Xr |
Analog Amplifier | - | - | - | - | - | - | X | X | X | X |
Analog Differential trigger | - | - | - | - | - | - | X | X | X | X |
Analog multiplexer | - | - | - | - | - | - | - | X | X | X |
PI Controller | - | - | - | - | - | - | - | Xr | Xr | Xr |
Analog Ramp | - | - | - | - | - | - | - | - | X | X |
Pulse width moderator (PWM) | - | - | - | - | - | - | - | - | X | X |
Mathmatic instruction | - | - | - | - | - | - | - | - | X | X |
Mathmatic instruction error detection | - | - | - | - | - | - | - | - | X | X |
Astronomical clock | - | - | - | - | - | - | - | - | - | X |
Stopwatch | - | - | - | - | - | - | - | - | - | Xr |
Analog filter | - | - | - | - | - | - | - | - | - | X |
Max/Min | - | - | - | - | - | - | - | - | - | Xr |
Average value | - | - | - | - | - | - | - | - | Xr | |